Section 5704.2.9.6.1 of the CFC, Geographic limits in which the storage of Class I and Class II liquids in above-ground tanks outside of buildings is prohibited, is amended to read as follows:

Section 5704.2.9.6.1 (Geographic limits in which the storage of Class I and Class II liquids in above-ground tanks outside of buildings is prohibited): areas of the city of Bakersfield which represent residential and commercial designations according to the city of Bakersfield planning department zoning map will be limited in the storage of flammable and combustible liquids as follows:

A. Dispensing of fuel from an approved above ground storage tank shall be limited to two thousand (2,000) gallons tank capacity.

(Ord. 5119 § 1, 2023; Ord. 4997 § 1, 2019; Ord. 4877 § 1, 2016; Ord. 4739 § 1, 2013; Ord. 4636 § 1, 2010; Ord. 4474 § 1, 2007)